Warranty: | 12 Months |
---|---|
Phase: | Dual |
Output Power: | 10kw |
Customization: |
---|
Shipping Cost:
Estimated freight per unit. |
about shipping cost and estimated delivery time. |
---|
Payment Method: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Initial Payment Full Payment |
Currency: | US$ |
---|
Return&refunds: | You can apply for a refund up to 30 days after receipt of the products. |
---|
Suppliers with verified business licenses
MODEL
|
TT 10KW
|
|
RATED POWER
|
10000 W
|
|
PV INPUT (DC)
|
|
|
Maximum DC Power
|
14850 W
|
|
Nominal DC Voltage
|
720 VDC
|
|
Maximum DC Voltage
|
900 VDC
|
|
Working DC Voltage Range
|
300 VDC ~ 900 VDC
|
|
Start-up Voltage / Initial Feeding Voltage
|
320 VDC / 350 VDC
|
|
MPP Voltage Range
|
350 VDC ~ 850 VDC
|
|
Maximum Input Current
|
2*18.6 A
|
|
Isc PV (absolute maximum)
|
25 A
|
|
Max. inverter back feed current to the array
|
0 A
|
|
GRID OUTPUT (AC)
|
|
|
Nominal Output Voltage
|
230 VAC (P-N) / 400 VAC (P-P)
|
|
Output Voltage Range
|
184 - 265 VAC per phase
|
|
Output Frequency Range
|
47.5 ~ 51.5 Hz or 59.3~ 60.5Hz
|
|
Nominal Output Current
|
14.5 A per phase
|
|
Inrush Current/Duration
|
17 A per phase / 20ms
|
|
Maximum Output Fault Current/Duration
|
51 A per phase / 1ms
|
|
Maximum output Overcurrent Protection
|
51 A per phase
|
|
Power Factor Range
|
0.9 lead - 0.9 lag
|
|
AC INPUT
|
|
|
AC Start-up Voltage
|
120-140 VAC per phase
|
|
Auto Restart Voltage
|
180 VAC per phase
|
|
Acceptable Input Voltage Range
|
170 - 280 VAC per phase
|
|
Nominal Frequency
|
50 Hz / 60 Hz
|
|
AC Input Power
|
10000VA/10000W
|
|
Maximum AC Input Current
|
25 A
|
|
Inrush Input Current
|
25 A / 1ms
|
|
BATTERY MODE OUTPUT (AC)
|
|
|
Nominal Output Voltage
|
230 VAC (P-N) / 400 VAC (P-P)
|
|
Output Frequency
|
50 Hz / 60 Hz (auto sensing)
|
|
Output Waveform
|
Pure sine wave
|
|
Output Power
|
10000VA/10000W
|
|
Efficiency (DC to AC)
|
91%
|
|
BATTERY & CHARGER (Lead-acid/Li-ion)
|
|
|
DC Voltage Range
|
40 - 60 VDC
|
|
Nominal DC Voltage
|
48 VDC
|
|
Maximum Battery Discharging Current
|
275 A
|
|
Maximum Charging Current
|
200 A
|
Suppliers with verified business licenses